Air Circuit Breaker QKW2-2000

Air circuit breaker for AC 50Hz systems (≤690V, 630A–4000A), providing power distribution and system protection against overload, over/undervoltage, short-circuit, and single-phase earth faults. Features intelligent selective protection and open communication interfaces supporting “Four Tele” functions (telemetry, telesignaling, telecontrol, teleregulation) for automation systems. Compliant with GB/T 14048.2 and IEC 60947-2.

Share to:

Usage Details

The QKW2 Series Air Circuit Breaker (hereinafter referred to as the “circuit breaker”) is designed for power distribution systems with AC 50Hz, rated voltage up to AC 690V and below, covering a rated current range from 630A to 4000A. This product performs dual functions of power distribution and system protection in electrical networks, effectively safeguarding circuits and power supply equipment against damage caused by faults such as overload, overvoltage/undervoltage, short circuit, and single-phase earth faults.

The circuit breaker is equipped with intelligent protection functions, providing precise selective protection to enhance power supply reliability and avoid unnecessary power outages. Additionally, it features an open communication interface capable of supporting “Four Tele” functions—telemetry, telesignaling, telecontrol, and teleregulation—to meet the requirements of control centers and automation systems.

This series of circuit breakers strictly complies with the technical specifications of the national standard GB/T 14048.2 and the international standard IEC 60947-2 “Low-voltage switchgear and controlgear – Part 2: Circuit-breakers,” ensuring industry-leading performance in safety, reliability, and compatibility.

Configuration

Mounting Types: Fixed Type, Drawout Type
Number of Poles: 3-Pole, 4-Pole
Operation Methods: Motor Spring-Charged Operation, Manual Spring-Charged Operation (Manual charging is primarily used for inspection and maintenance)
Types of Trip Units: Intelligent Controller, Undervoltage Instantaneous (Time-delayed) Release, Shunt Release

Intelligent Controller Functions

a. Intelligent controllers are available in two models: M-Type (Basic) and H-Type (Communication).
b. Features include: long-time delay inverse-time for overload, short-time delay inverse-time/definite-time, and instantaneous tripping functions. Users can configure these settings to achieve the desired protection characteristics.
c. Equipped with single-phase earth fault protection function.
d. Display functions: current display and voltage display (please specify when ordering).
e. Alarm function: overload pre-alarm.
f. Self-check functions: thermal self-check and microprocessor self-diagnosis.
g. Test function: allows testing of the controller’s tripping characteristics.

Selection Guide

Product NameFrame SizeRated CurrentPolesMounting TypeControl Circuit Voltage
QKW21600
2000
3200
6300
See Table 33: 3P
4: 4P
DH: Draw-out Horizontal
FH: Fixed Horizontal
AC220V
AC380V
DC220V
AC220V (without undervoltage release)
AC380V (without undervoltage release)
DC220V (without undervoltage release)

Table 2: Accessory Selectio

Product NameFrame SizeAccessory NameAccessory Operating Voltage
QKW21600
2000
3200
6300
See Accessory Name ListAC380: 380V AC
AC220: 220V AC
DC220: 220V DC
DC110: 110V DC

Accessory Name List

CategoryAccessory CodeDescription
Release AccessoriesQKWLL-type release
QKWLAL-type release with MCR and zone selective interlocking (ZSI)
QKWLBL-type release with DO signal alarm
QKWMAM-type release with MCR and ZSI
QKWMRM-type release with DO signal alarm
QKWMMUM-type release with voltmeter
QKWHH-type release
QKWHPH-type release with power meter and advanced voltage protection
QKWHHH-type release with harmonic meter
QKWHCOMH-type release with communication function
QKW2AD1DC power supply module (for QKW2630~6300)
QKW2AD4Power supply module (for QKW2630~6300)
QKW2EC/N201Relay module (with communication, for QKW2630~6300201)
QKW2ZCT1Earth leakage current transformer (for QKW2630~6300)
QKW2NCTPhase-to-phase current transformer (for QKW2630~6300N)
QKW2ZTIOOEarthing current transformer (for QKW2630~6300)
Remote Control & MonitoringMXShunt trip coil
MNUndervoltage release coil
MNRTime-delay undervoltage release coil
XFClosing coil
MCHMotor operator mechanism
OFAuxiliary switch (6 NO & 6 NC)
ACSecondary wiring (51 circuits, replaces standard 47 circuits)
Installation & ConnectionEIPPhase-to-phase partition plate
CDPDoor frame
Locking & Interlocking MechanismsLK11 lock with 1 key
LK211 lock with 2 keys
LK323 locks with 2 keys
ILL2Cable interlock (for 2 units)
ILL2Lever interlock (for 2 units)
DLKDoor interlock (for draw-out type products)

Table 3: Technical Parameters

ItemQKW2-1600QKW2-2000QKW2-3200QKW2-6300
Frame Size1600200032006300
Rated Impulse Withstand Voltage (Uimp, kV)12688
Rated Insulation Voltage (Ui, V)1000100010001000
Poles3, 43, 43, 43, 4
Rated Operating Voltage (Ue, V)AC400/690, 50HzAC400/690, 50HzAC400/690, 50HzAC400/690, 50Hz
Arc Flash Distance (mm)05000
National StandardGB/T 14048.2GB/T 14048.2GB/T 14048.2GB/T 14048.2
International StandardIEC 60947-1, IEC 60947-2IEC 60947-1, IEC 60947-2IEC 60947-1, IEC 60947-2IEC 60947-1, IEC 60947-2
Utilization CategoryBBBB
Rated Current (In, A)100, 200, 250, 315, 400, 500, 630, 800, 1000, 1250, 1600400, 630, 800, 1000, 1250, 1600, 20002000, 2500, 2900, 3200, 3600, 4000 (uprated)4000, 5000, 6300
Rated Ultimate Short-circuit Breaking Capacity (Icu, kA)AC400V: 65
AC690V: 50
AC400V: 80
AC690V: 50
AC400V: 100AC400V:120
AC690V: 85
Rated Service Short-circuit Breaking Capacity (Ics, kA)AC400V: 55
AC690V: 42
AC400V: 65
AC690V: 40
AC400V: 80AC400V:100
AC690V: 75
Rated Short-time Withstand Current (Icw, kA/1s)AC400V: 50
AC690V: 42
AC400V: 65
AC690V: 40
AC400V: 80AC400V:100
AC690V: 75
MaintenanceMechanical4500450045004500
Electrical500500500500
Ambient TemperatureUpper limit ≤40°C, lower limit ≥-5°C; average in 24h ≤35°CUpper limit ≤40°C, lower limit ≥-5°C; average in 24h ≤35°CUpper limit ≤40°C, lower limit ≥-5°C; average in 24h ≤35°CUpper limit ≤40°C, lower limit ≥-5°C; average in 24h ≤35°C
AltitudeNot exceeding 2000mNot exceeding 2000mNot exceeding 2000mNot exceeding 2000m
Ambient Humidity≤50% at 40°C; can be relatively higher at lower temperatures≤50% at 40°C; can be relatively higher at lower temperatures≤50% at 40°C; can be relatively higher at lower temperatures≤50% at 40°C; can be relatively higher at lower temperatures
Pollution DegreeIIIIIIIIIIII
Installation PositionVertical or inclined at any angle not exceeding 5°Vertical or inclined at any angle not exceeding 5°Vertical or inclined at any angle not exceeding 5°Vertical or inclined at any angle not exceeding 5°