HD11 Open Knife Switch

HD open and HS dual-throw switches for AC 50Hz (400V AC/230V DC, 630A) distribution gear. Arc-extinguishing models handle load switching; others for isolation. Compact, easy to operate, compliant with IEC 60947-3/GB/T 14048.3. HD11 for power station non-load switching and isolation.

Share to:

Application Scope

The HD series open knife switch and HS series dual-throw switch (hereinafter referred to as “switches”) are suitable for AC 50Hz systems with a rated voltage up to AC 400V and DC 230V, and rated thermal current up to 630A in complete distribution equipment.

Switches with an arc-extinguishing cover are mainly used for making and breaking circuits under load.
Switches without an arc-extinguishing cover are primarily used for circuit isolation.

The products feature a simple structure, convenient operation, and comply with IEC 60947-3 and GB/T 14048.3 standards.

The HD11 series center-handle knife switch is mainly used in power stations to make or break non-load circuits and serves as a power isolation switch.

Normal Operating Conditions

  1. Ambient air temperature:
    • Maximum: +40°C
    • Minimum: -5°C
    • 24-hour average temperature shall not exceed +35°C
  2. Altitude: Installation site not exceeding 2000 meters above sea level.
  3. Atmospheric conditions:
    • Relative humidity not exceeding 50% at +40°C
    • Higher humidity allowed at lower temperatures (e.g., up to 90% at +20°C)
    • Condensation due to temperature variation should be considered
  4. Pollution degree: Grade 3
  5. Installation category: Class III
  6. Installation environment:
    Installed in locations free from severe vibration and impact, free from explosive hazards, and without corrosive gases that could damage metal or insulation materials.
  7. For special operating conditions, please consult the manufacturer.

Model & Designation

HD □ □ □ – □ / □

  • HD – Open Knife Switch (single-throw)
  • Design Code
    • 11: Center handle type
  • Arc Protection Type
    • F: With arc-extinguishing cover
    • FA: Protective type (with protective cover)
  • Rated Thermal Current
  • Number of Poles
    • 2P / 3P / 4P
  • Connection Method
    • 8: Board-front wiring

Structural Features

  • For ratings 200A and 400A, single-break structure is adopted; 600A models use double-break structure.
  • All blades are equipped with springs to ensure sufficient contact pressure.
  • Blade, contact bridge, and contact surfaces are tin-plated to reduce surface contact resistance and improve conductivity.
  • The operating mechanism of switches with arc-extinguishing cover ensures safe operation when switching load circuits. The cover is made of insulating material and arc-resistant components, significantly enhancing arc suppression capability.
  • The center-handle operating mechanism features fast make-and-break action to improve safety performance. The breaking and making speed of 200A switches is the same as that of 600A switches.
  • The switch adopts a visible isolation structure with clearly observable contact position and status indication.
  • The insulating base plate and arc barriers are made of high-strength insulating materials, offering excellent mechanical strength and electrical performance.

Technical Specifications

Parameter100A200A400A600A
Rated Thermal Current (Ith)100A200A400A600A
Rated Insulation Voltage (Ui)1000V1000V660V660V
Rated Operating Voltage (Ue)400V / 690V400V / 690VAC400V, DC230VAC400V, DC230V
Rated Frequency50Hz50Hz50Hz50Hz
Utilization CategoryAC-22AAC-22AAC-20, AC-23AC-20, AC-23
Rated Breaking Capacity (r.m.s)1kA2kA4kA6kA
Rated Making Capacity (r.m.s)1kA1.6kA3.2kA4.8kA
1s Short-Time Withstand Current (r.m.s)5kA10kA20kA25kA
Mechanical Life (operations)20,00010,00010,0005,000
Electrical Life (operations)2,0001,0001,000800
Operating Force (F)≤ 80N≤ 250N≤ 300N≤ 350N

Note: Rated breaking and making capacity as well as utilization category AC-23 apply only to switches equipped with arc-extinguishing cover.

Overall Dimensions and Installation Size

1.HD11 Series Overall Dimensions and Mounting Dimensions

image

HD11/8 (Front Panel) Series

image

HD11/9 (Rear Panel) Series

Dimensions and Installation Size (mm)

HD11-200 Series

PolesAB/B*CC1DE*ab/b*ΦcTerminal Cross SectionBolt (M)
2P60123110220703212014073.5 × 24.5M8
3P190205 / 20511022070327014073.5 × 24.5M8
4P265230 / 230118238703214014073.5 × 24.5M8

HD11-400 Series

PolesAB/B*CC1DE*ab/b*ΦcTerminal Cross SectionBolt (M)
2P190265 / 265132270804316019074.2 × 36.5M12
3P220265 / 26513227080438019074.2 × 36.5M12
4P300272 / 272130265804316019074.2 × 36.5M12

HD11-600 Series

PolesAB/B*CC1DE*ab/b*ΦcTerminal Cross SectionBolt (M)
2P240325 / 2701123051005520014097 × 39M16
3P270325 / 27011230510055100140 / 22097 × 39M16
4P370325 / 2701123051005520014097 × 39M16

Note: Dimensions marked with “*” refer to the rear-panel mounting type.

HD11F Series Dimensions and Mounting Dimensions

image

HD11F Series Dimensions and Mounting Dimensions (mm)

HD11F-100

PolesABCC1DEabΦcTerminal Cross SectionBolt (M)
2P60123–13532–64674.5–M4
4P124123–13532–64674.5–M4

HD11F-200

PolesABCC1DEabΦcTerminal Cross SectionBolt (M)
2P160205110220703212014073.2 × 24.5M8
3P19020511022070327014073.2 × 24.5M8
4P265230118238703214014073.2 × 24.5M8

HD11F-400

PolesABCC1DEabΦcTerminal Cross SectionBolt (M)
2P190265132270804316019073.5 × 36.5M12
3P22026513227080438019073.5 × 36.5M12
4P300272130265804316019073.5 × 36.5M12