QKM1LE-800M

Engineered for AC 50Hz circuits (400V, 40A–630A), the OKM1LE series provides comprehensive protection against electric shock, earth fault-induced fires, overloads, and short circuits. It supports both vertical and horizontal installation and functions as an infrequent line switch, complying with GB/T 14048.2 standards.

Share to:

Scope of Application

The OKM1LE series Residual Current Operated Circuit Breaker (here in after referred to as the circuit breaker) is suitable for circuits with AC 50Hz, rated voltage up to 400V, and rated current from 40A to 630A. Its main function is to provide indirect contact protection against fatal electric shock hazards. It can also be used to prevent electrical fires caused by earth fault currents. Additionally, it can protect lines against overload and short circuit, and can serve for the infrequent switching of lines.

The residual current operated circuit breaker can be installed vertically (upright mounting) or horizontally (side mounting).

The circuit breaker complies with the standard: GB/T 14048.2 “Low-voltage switchgear and controlgear – Part 2: Circuit-breakers”.

Technical Parameters

ModelFrame Current Rating (A)Rated Current In (A)Rated Operational Voltage Ue (V)PolesRated Residual Operating Current IΔn (mA)Rated Residual Non-Operating Current IΔno (mA)Ultimate Short-Circuit Breaking Capacity Icu (kA)Service Short-Circuit Breaking Capacity Ics (kA)Arcing Distance (mm)Rated Insulation Voltage Ui (V)Rated Impulse Withstand Voltage Uimp (kV)
OKM1LE-10010016, 20, 25, 40, 50, 63, 80, 1004003, 4100, 300, 50050, 150, 2503522≤506908
OKM1LE-250250100, 125, 140, 160, 180, 200, 225, 2504003, 4100, 300, 50050, 150, 2505035≤508006
OKM1LE-400400225, 250, 315, 350, 4004003, 4100, 300, 50050, 150, 2506542≤1006908
OKM1LE-630630400, 500, 6304003, 4100, 300, 50050, 150, 2507045≤1006908

Note: The three-level residual operating current adjustment can be selected arbitrarily by the user.

CONTACT FOR FREE SAMPLE

Scroll to Top

Request a Technical Quote

Technical Tip: For guaranteed form delivery, we recommend disabling Private/Incognito mode.