QKM3L-250

IoT-enabled circuit breaker for AC 50Hz distribution protection (up to 400V, 800A, 1000V insulation). Provides comprehensive protection (overload, short-circuit, residual current, over/undervoltage, phase loss) and real-time monitoring of current, voltage, power, energy, and terminal temperature. Features power line carrier communication and network topology identification, supporting smart grid operation and maintenance. Compliant with GB/T 14048.2 and DL/T standards.

Share to:

IoT-enabled Intelligent Circuit Breaker (hereinafter referred to as the circuit breaker) is suitable for distribution protection with AC 50Hz, rated operating current up to 800A, rated insulation voltage 1000V, and rated operating voltage AC400V.

The circuit breaker provides long-time delay, short-time delay, instantaneous, residual current, over/undervoltage, and phase loss protection functions to protect lines and power equipment. It can feed back information such as current, voltage, power, energy, and terminal temperature of the product to the terminal equipment in the distribution area with meter-level accuracy, which is used for detection and monitoring of the load side, reduces the operation and maintenance cost of the power grid, and provides necessary data for future intelligent distribution area systems. The circuit breaker also has the functions of automatic identification of the topological relationship of the distribution network in the area and power line carrier communication.

This product complies with the standards: GB/T 14048.2, DL/T 20.., and the communication protocol for residual current protectors.

ItemQKM3L-125QKM3L-160 / QKM3L-250QKM3L-400QKM3L-630QKM3L-800
Rated Current In (A)Adjustable 50A–125AAdjustable 63A–160A / 100A–250AAdjustable 160A–400AAdjustable 260A–630AAdjustable 260A–800A
Rated Impulse Withstand Voltage Uimp (kV)88888
Rated Insulation Voltage Ui (V)10001000100010001000
Rated Operating Voltage Ue (V)AC400AC400AC400AC400AC400
Pole Number3P+N3P+N3P+N3P+N3P+N
Selectivity ClassAABBBB
Breaking Capacity Rating/S/MHLS/MH/MS/MH
Rated Ultimate Short-circuit Breaking Capacity Icu AC400V (kA)AC 400V50355065852035658585658550658585
Rated Service Short-circuit Breaking Capacity Ics AC400V (kA)AC 400V35353550701535455570455550456570
Rated Short-time Withstand Current Icw1.25kA/1s3kA/0.5s 10kA/1s5kA/0.5s8kA/0.5s10kA/1s
Rated Residual Current IΔn (A)Adjustable 30mA–1000mAAdjustable 30mA–1000mAAdjustable 30mA–1000mAAdjustable 30mA–1000mAAdjustable 30mA–1000mA
Trip Time (Non-operating)0.065s, 0.1s, 0.2s0.065s, 0.1s, 0.2s0.065s, 0.1s, 0.2s0.065s, 0.1s, 0.2s0.065s, 0.1s, 0.2s
Rated Residual Current Make-and-break Capacity ΔIcm25%Icu25%Icu25%Icu25%Icu25%Icu
Mechanical Endurance (times)1000010000500050005000
Electrical Endurance (times)20002000120012001200
Overall Dimensions (L×W×H, mm)220×122×135240×142×138336×198×182336×198×182355×240×191
Main Technical Parameters (English Professional Version)
ItemUnitQKM3L-125AQKM3L-250AQKM3L-400AQKM3L-630AQKM3L-800A
Model–QKM3L-125AQKM3L-250AQKM3L-400AQKM3L-630AQKM3L-800A
Frame Grade Rated Current (Inm)A125250400630800
Applicable Pole Number–3P+N
Rated Working Voltage (Ue)V/HzAC400V, 50Hz
Rated Current (In)A0.4–1.0×Inm (continuously adjustable)
Rated Insulation Voltage (Ui)V1000
Rated Impulse Withstand Voltage (Uimp)V8000
Rated Ultimate Short-Circuit Breaking Capacity (Icu)kA36 (M); 50 (H)35 (S); 50; 65 (M)35 (S); 65; 85 (M)65; 85 (M)50 (S); 65; 85 (M)
Rated Operational Short-Circuit Breaking Capacity (Ics)kA25 (M); 35 (H)35 (S); 35; 50 (M)35 (S); 45; 55 (M)45; 55 (M)50 (S); 45; 65 (M)
Rated Short-Time Withstand Current (Icw)kA/s1.25/13/0.55/0.58/0.510/1
Overload Delay Time Coefficients3–18 (adjustable)
Short-Circuit Short-Time Delay Multiple (×In)–2–10 (adjustable)
Short-Circuit Short-Time Delay Timems100–400 (continuously adjustable)
Short-Circuit Instantaneous Multiple (×In)–4–12 (adjustable)
Overvoltage Trip ValueVDefault: 275±1% (user configurable)
Undervoltage Trip ValueVDefault: 165±1% (user configurable)
Phase Loss Trip ValueVDefault: 120±1% (user configurable)
Rated Residual Operating Current (IΔn)mA30–1000mA (8 sets customizable)
Rated Residual Non-Operating Current (IΔno)mAIΔno = 70% × IΔn
Limit Non-Drive Times0.06 / 0.1 / 0.2
Residual Current Operating Characteristic–AC Type
Rated Residual Short-Circuit Making & Breaking Capacity (IΔm)kAIΔm = 25% × Icu
Utilization Category–Class AClass AClass BClass BClass B